DonateLog in
River Hub
Why it keeps happening

Before the works

An overflow that spills while its own treatment works stays shut is not being overwhelmed by rain — the problem is upstream of the works, and local.

If the sewer network were genuinely overwhelmed by rainfall, the treatment works' own storm overflow would be discharging too.

When an upstream overflow spills on a day its works did not, the works still had capacity — so the discharge points to a blockage, a failed pump, or infiltration on that branch, not to a works too small for its catchment. That changes who pays and how fast: a branch fault is maintenance, chargeable now, not a capital scheme waiting for the next five-year price review.

OverflowEventsIts worksOn record
Trerhyngyll Overflow1Cowbridge STWMeasure linked
Wenvoe Overflow1Cardiff (west) And Barry (cog Moors)Measure linked
Sully Moors Road Storm Overflow1Cardiff (west) And Barry (cog Moors)Measure linked
Cwm Barry Storm Overflow1Cardiff (west) And Barry (cog Moors)Measure linked
Harbour Road Barry Town Storm Overflow1Cardiff (west) And Barry (cog Moors)Measure linked
Llantwit Major Beach Road Storm Overflow1Llantwit MajorMeasure linked
Countess Place Penarth Overflow1Cardiff (west) And Barry (cog Moors)Measure linked
Nant Talwg Storm Overflow1Cardiff (west) And Barry (cog Moors)Measure linked
Torbay Terrace Junction Storm Overflow1Cardiff (west) And Barry (cog Moors)Measure linked
Hillary Rise Rear Storm Overflow1Cardiff (west) And Barry (cog Moors)Measure linked
Millfield Drive Storm Overflow1Cowbridge STWMeasure linked
Cornerswell Road Penarth Storm Overflow1Cardiff (west) And Barry (cog Moors)No measure
B4265 Storm Overflow1West Aberthaw OutfallMeasure linked
Rock Road Storm Overflow1West Aberthaw OutfallMeasure linked
Rhoose Storm Overflow1Cardiff (west) And Barry (cog Moors)Measure linked
Craig Penllyne Storm Overflow1Cowbridge STWMeasure linked
Brockhill Rise Storm Overflow1Cardiff (west) And Barry (cog Moors)Measure linked

What this needs to be reliable

The comparison needs both monitors working. Where a works' own overflow monitor was offline we record no result rather than a pre-works spill, so this is a floor. A treatment works itself is excluded — it is the end of the line and cannot spill before the works. Two works in the catchment have no monitored overflow at all, so their upstream overflows are listed as not assessed, not as clean.