DonateLog in
River Hub
NRW sampling point

Highwayman Pub Inn

Sampled by Natural Resources Wales on 13 visits from 2024 to 2026.

Ammonia

2024–2026: avg 1.216 · max 2.720 mg/l
0246202520262024-02-08: below 0.5 mg/l2025-06-02: 2.72 mg/l2025-11-10: 1.09 mg/l2026-01-13: 1.21 mg/l2026-05-27: 0.81 mg/l
High ≤ 0.2Good ≤ 0.3Moderate ≤ 0.75Poor ≤ 1.1Bad > 1.1

Dissolved oxygen

2024–2026: avg 46 · min 29 % saturation
20406080100120202520262024-02-08: 28.5 % saturation2025-06-02: 32.2 % saturation2025-11-10: 55.1 % saturation2026-01-13: 51.4 % saturation2026-05-27: 61.1 % saturation
High ≥ 80Good ≥ 75Moderate ≥ 64Poor ≥ 50Bad < 50

Water temperature

13.4–22.2 °C

Warm water holds less oxygen. There is no river standard for temperature here.

0102030202520262024-02-08: 14.2 °C2025-06-02: 22 °C2025-11-10: 18.5 °C2026-01-13: 13.4 °C2026-05-27: 22.2 °C

Shading shows the Water Framework Directive river standards. Hollow dots are readings below the lab’s detection limit, drawn at the limit; averages count them at half the limit. Bands are indicative:Natural Resources Wales’s formal classification also uses percentiles and, for phosphate, limits set for each stretch of river.

Every reading: BOD : 5 Day ATU (mg/l)

NRW sampling point S5830136 · 71 readings of 9 tests since 2023.

DateResultUnitSample
2026-05-27 11:227.77mg/lFINAL SEWAGE EFFLUENT · COMPLIANCE AUDIT (PERMIT)
2026-01-13 13:1319.7mg/lFINAL SEWAGE EFFLUENT · COMPLIANCE AUDIT (PERMIT)
2025-11-10 13:5514.3mg/lFINAL SEWAGE EFFLUENT · COMPLIANCE AUDIT (PERMIT)
2025-06-02 13:5218.5mg/lFINAL SEWAGE EFFLUENT · COMPLIANCE AUDIT (PERMIT)
2024-02-08 11:3052mg/lFINAL SEWAGE EFFLUENT · COMPLIANCE AUDIT (PERMIT)
2023-11-20 12:4431.4mg/lFINAL SEWAGE EFFLUENT · COMPLIANCE AUDIT (PERMIT)
2023-08-14 11:5017mg/lFINAL SEWAGE EFFLUENT · COMPLIANCE AUDIT (PERMIT)
2023-05-31 11:2821.6mg/lFINAL SEWAGE EFFLUENT · COMPLIANCE AUDIT (PERMIT)
2023-02-09 12:2513.6mg/lFINAL SEWAGE EFFLUENT · COMPLIANCE AUDIT (PERMIT)

Source: Natural Resources Wales Open Water Quality Archive, Open Government Licence. The regulator’s own monitoring of the Thaw and Cadoxton.