NRW sampling point

Stp @ Llechwen Hall Hotel, Llanfabon

Sampled by Natural Resources Wales on 10 visits from 2024 to 2026.

Dissolved oxygen

2024–2026: avg 21 · min 1 % saturation
0255075100125202520262026-01-15: 22.7 % saturation2026-04-14: 34.4 % saturation2026-05-12: 38.5 % saturation2026-06-01: 21.9 % saturation2026-08-03: 1.4 % saturation2026-09-08: 5.7 % saturation
High ≥ 80Good ≥ 75Moderate ≥ 64Poor ≥ 50Bad < 50

Water temperature

16.0–25.8 °C

Warm water holds less oxygen. There is no river standard for temperature here.

0204060202520262026-01-15: 16 °C2026-04-14: 19.1 °C2026-05-12: 21.7 °C2026-06-01: 24.2 °C2026-08-03: 25.8 °C2026-09-08: 25.4 °C

Shading shows the Water Framework Directive river standards. Hollow dots are readings below the lab’s detection limit, drawn at the limit; averages count them at half the limit. Bands are indicative:Natural Resources Wales’s formal classification also uses percentiles and, for phosphate, limits set for each stretch of river.

Every reading: BOD : 5 Day ATU (mg/l)

NRW sampling point S42208 · 45 readings of 8 tests since 2026.

DateResultUnitSample
2026-09-08 09:3745.8mg/lFINAL SEWAGE EFFLUENT · COMPLIANCE AUDIT (PERMIT)
2026-08-03 11:03230mg/lFINAL SEWAGE EFFLUENT · COMPLIANCE AUDIT (PERMIT)
2026-06-01 11:1656.7mg/lFINAL SEWAGE EFFLUENT · COMPLIANCE AUDIT (PERMIT)
2026-05-12 11:2339.5mg/lFINAL SEWAGE EFFLUENT · COMPLIANCE AUDIT (PERMIT)
2026-04-14 11:2354.7mg/lFINAL SEWAGE EFFLUENT · COMPLIANCE AUDIT (PERMIT)
2026-01-15 09:4367.2mg/lFINAL SEWAGE EFFLUENT · COMPLIANCE AUDIT (PERMIT)

Source: Natural Resources Wales Open Water Quality Archive, Open Government Licence. The regulator’s own monitoring of the River Taff.