Why it keeps happening

Before the works

An overflow that spills while its own treatment works stays shut is not being overwhelmed by rain — the problem is upstream of the works, and local.

If the sewer network were genuinely overwhelmed by rainfall, the treatment works' own storm overflow would be discharging too.

When an upstream overflow spills on a day its works did not, the works still had capacity — so the discharge points to a blockage, a failed pump, or infiltration on that branch, not to a works too small for its catchment. That changes who pays and how fast: a branch fault is maintenance, chargeable now, not a capital scheme waiting for the next five-year price review.

OverflowEventsIts worksOn record
East Budleigh pumping stationPS-CSO335Otterton STWNo measure
Gittisham pumping stationPS-CSO/EO249Feniton STWNo measure
Glebe Farm pumping station, BuckerellPS-CSO/EO239Honiton STWNo measure
Millmoor Ln, Newton PopplefordCSO238Otterton STWNo measure
The Ham pumping station, Sidmouth 2PS-CSO/EO215Sidmouth STWNo measure
Tipton St John pumping station, SidmouthPS-CSO/EO75Fluxton STWNo measure
Awliscombe pumping stationPS-CSO/EO75Honiton STWNo measure
Fortescue, SidmouthCSO74Sidmouth STWMeasure linked
The Green, OttertonCSO60Otterton STWNo measure
Broadhembury pumping stationPS-CSO/EO58Honiton STWNo measure
Exeter Road, HonitonCSO56Honiton STWNo measure
Weston pumping station, HonitonPS-CSO/EO53Honiton STWNo measure
West Bank pumping station, Ottery St MaryPS-CSO/EO44Fluxton STWNo measure
Ottery St Mary Atten TankSO33Fluxton STWNo measure
Manstone Ln, SidmouthCSO32Sidmouth STWMeasure linked
Rec Ground, Newton PopplefordCSO22Otterton STWNo measure
Butts Hill pumping station, Ottery St MaryPS-CSO/EO12Fluxton STWNo measure
Buckerell Manhole pumping stationPS-CSO/EO8Honiton STWNo measure
High Street, HonitonCSO7Honiton STWNo measure
27 Oaklea, HonitonCSO6Honiton STWNo measure
Chapel Lane, Ottery St MaryCSO5Fluxton STWNo measure
Batts Lane, Ottery St. MaryCSO3Fluxton STWNo measure
Temple St, SidmouthCSO3Sidmouth STWNo measure
Castle Copse pumping station, Ottery St MaryPS-CSO/EO2Fluxton STWNo measure
Byes Ln, SidfordCSO2Sidmouth STWNo measure
Vicarage Rd, SidmouthCSO2Sidmouth STWNo measure

What this needs to be reliable

The comparison needs both monitors working. Where a works' own overflow monitor was offline we record no result rather than a pre-works spill, so this is a floor. A treatment works itself is excluded — it is the end of the line and cannot spill before the works. Two works in the catchment have no monitored overflow at all, so their upstream overflows are listed as not assessed, not as clean.