Who is fixing it

What the regulator requires

A measure is a specific action the regulator requires the water company to take at a named site — to investigate a problem, keep monitoring it, or physically fix it — each with a completion date. These are the legally binding measures on record for this catchment: what each requires, and what to watch.

These measures are legally binding. Each one is a dated, site-specific requirement the company must deliver.

The Water Industry National Environment Programme is how the Environment Agency turns statutory duties into named obligations at named sites, with a completion date attached. Where a measure requires a physical upgrade, the Agency writes the result into the site's environmental permit — and from that point the requirement is criminally enforceable.

The measure itself is public. What is not published is the water company's action to comply with it — its delivery is reported to the regulator and scored, but the underlying work, and whether a measure has actually resolved the problem on the ground, is not on the public record. What to watch is slippage: a measure can be re-dated or re-scoped, and until the permit is varied the obligation has not changed.

What the types mean

Improvement

A physical upgrade — bigger storage, better treatment, more capacity. This is the only type that actually fixes the problem on the ground.

Investigation

A study of the cause. It produces a report, not a repair — an investigation must lead to an improvement before anything changes.

Monitoring

Installing or running instruments to measure the problem. Necessary evidence, but on its own it fixes nothing — it too has to be followed by an improvement.

So an overflow whose only measures are investigations or monitoring is being looked at, not yet fixed. On the gaps page, only a measure that is still active counts as action — a measure completed while the overflow is still failing does not.

34
Measures in this catchment
WINEP, current record
29
Still active
not yet past their date
5
Assumed complete
completion date has passed
5
Are physical improvements
the rest investigate or monitor
ReferenceDriverTypeWhat it requiresStatusAttached to
08TW100529 · aU_MON3Monitoring
MCERTS certification of an AMP7 U_MON3 driver output overflow operation monitor (U_MON3a)
Burstow wwtw
Complete 2025-26Burstow Stream
08TW100530 · aU_MON3Monitoring
MCERTS certification of an AMP7 U_MON3 driver output overflow operation monitor (U_MON3a)
Crawley wwtw
Complete 2025-26Tilgate Brook and Gatwick Stream at Crawley
08TW100531 · aU_MON3Monitoring
MCERTS certification of an AMP7 U_MON3 driver output overflow operation monitor (U_MON3a)
Esher wwtw
Complete 2025-26Esher STW
08TW100533 · aU_MON3Monitoring
MCERTS certification of an AMP7 U_MON3 driver output overflow operation monitor (U_MON3a)
Holmwood wwtw
Complete 2025-26Leigh Brook
08TW100537 · aU_MON3Monitoring
MCERTS certification of an AMP7 U_MON3 driver output overflow operation monitor (U_MON3a)
Merstham wwtw
Complete 2025-26Redhill Brook
08TW101563 · aU_MON4Monitoring
Install and run event-duration monitoring
Burstow wwtw
Due 2026-27Burstow Stream
08TW100320 · aU_MON4Monitoring
Move AMP7 U_MON4 driver output to 2-minute flow monitoring (U_MON4a)
Crawley wwtw
Due 2026-27Tilgate Brook and Gatwick Stream at Crawley
08TW100330 · aU_MON4Monitoring
Move AMP7 U_MON4 driver output to 2-minute flow monitoring (U_MON4a)
Esher wwtw
Due 2026-27Esher STW
08TW100348 · aU_MON4Monitoring
Move AMP7 U_MON4 driver output to 2-minute flow monitoring (U_MON4a)
Holmwood wwtw
Due 2026-27Leigh Brook
08TW101565 · aU_MON4Monitoring
Install and run event-duration monitoring
Merstham wwtw
Due 2026-27Redhill Brook
08TW100377 · aU_MON4Monitoring
Move AMP7 U_MON4 driver output to 2-minute flow monitoring (U_MON4a)
Rusper wwtw
Due 2026-27Baldhorns Brook
08TW100484 · aWFD_NDLS_Chem1No deterioration
Holmwood STW cypermethrin load standstill limit
Holmwood STW
Due 2026-27Holmwood STW
08TW100142 · aWFD_NDLS_Chem2No deterioration
new PFOS limit
PFOS Crawley STW
Due 2026-27Tilgate Brook and Gatwick Stream at Crawley
08TW100067 · aWFD_NDLS_Chem1No deterioration
Burstow STW, cypermethrin, 0.0011949 ug
Reduce cypermethrin loading
Due 2026-27Burstow Stream
08TW100089 · aWFD_NDLS_Chem2No deterioration
Merstham STW, cypermethrin, 0.001 ug
Reduce cypermethrin loading
Due 2026-27Redhill Brook
08TW100056 · aWFD_NDLS_Chem2No deterioration
Burstow STW, aluminium (total), 1156.4
Reduce metal loading
Due 2026-27Burstow Stream
08TW100059 · aWFD_NDLS_Chem2No deterioration
Merstham STW, copper (dissolved), 6.33
Reduce metal loading
Due 2026-27Redhill Brook
08TW100127 · aWFD_NDLS_Chem2No deterioration
Merstham STW, Nonylphenol, 0.55µg/l
Reduce Nonylphenol loading
Due 2026-27Redhill Brook
08TW101545 · bWFD_INV_CHEMInvestigation
PFOS investigation - Crawley STW
4a Investigation to develop and trial a framework that meets statutory requirements
Due 2027-28Tilgate Brook and Gatwick Stream at Crawley
08TW101108 · gbEnvAct_INV4Investigation
Investigate the cause of the spills
Storm Overflows investigation at BROCKHAM BRIDGE SPS
Due 2027-28Tanners Brook (Holmewood to River Mole confluence at Brockham)
08TW101108 · fxEnvAct_INV4Investigation
Investigate the cause of the spills
Storm Overflows investigation at BURSTOW STW
Due 2027-28Burstow Stream
08TW101108 · gmEnvAct_INV4Investigation
Investigate the cause of the spills
Storm Overflows investigation at COMMONSIDE SPS
Due 2027-28Downside Ditches and Bookham Brook
08TW101108 · beEnvAct_INV4Investigation
Investigate the cause of the spills
Storm Overflows investigation at ESHER STW
Due 2027-28Mole (Hersham to R. Thames conf at East Molesey)
08TW101108 · boEnvAct_INV4Investigation
Investigate the cause of the spills
Storm Overflows investigation at HOLMWOOD STW
Due 2027-28Leigh Brook
08TW101108 · gaEnvAct_INV4Investigation
Investigate the cause of the spills
Storm Overflows investigation at RUSPER STW
Due 2027-28Baldhorns Brook
08TW101108 · azEnvAct_INV4Investigation
Investigate the cause of the spills
Storm Overflows investigation at SALFORDS , SURREY SPS
Due 2027-28Salfords Stream (Salfords to River Mole confluence)
08TW101108 · gcEnvAct_INV4Investigation
Investigate the cause of the spills
Storm Overflows investigation at SPOOKS HILL, NORTH HOLMWOOD CSO
Due 2027-28Tanners Brook (Holmewood to River Mole confluence at Brockham)
08TW100203 · aWFD_INV_MODInvestigation
Investigate the cause of the spills
WFD Investigation of in river Ecological Status to inform future action
Due 2027-28Rythe
08TW100200 · aWFD_INV_MODInvestigation
Investigate the cause of the spills
WFD Investigation of in river Ecological Status to inform future action
Due 2027-28Pipp Brook
10TW100024 · aU_IMP4Improvement
Storm Overflows improvements at HOLMWOOD STW
Storm Overflows action at HOLMWOOD STW
Due 2027-28Leigh Brook
08TW100893 · aEnvAct_IMP1Improvement
0.25 mg/l Phosphorus permit with stretch target of 0.1 mg/l at Crawley STW
Reduce Phosphorus Loadings at Crawley STW
Due 2029-30Tilgate Brook and Gatwick Stream at Crawley
08TW100902 · aEnvAct_IMP1Improvement
0.25 mg/l Phosphorus permit at Esher STW
Reduce Phosphorus Loadings at Esher STW
Due 2029-30Esher STW
08TW101113 · aENVAct_IMP2Improvement
Default scheme: Investigation and Solution in AMP 8: 1,285m3 storage, 20m3 screen
Storm Overflows action at Burstow STW SPS
Due 2029-30Burstow Stream
08TW101078 · aENVAct_IMP2Improvement
Default scheme: Investigation and Solution in AMP 8: 1,285m3 storage, No screen required
Storm Overflows action at Rusper Stw
Due 2029-30Baldhorns Brook

34 of 34 measures shown. A measure whose completion date has passed is shown as Complete; the water company's actual delivery against it is reported to the regulator but not published here.

There is no public change log

The live WINEP spreadsheet is internal, and there is no versioned public comparison or published reasons when a measure is re-dated or dropped. The only way to hold slippage to account is to archive every annual release and diff it yourself.

The 2027 pressure point

Most investigations must complete by 30 April 2027 to feed the 2030–35 programme. That date — not 2030 — is the one to hold: an investigation that slips past it cannot shape the next round of funded schemes.