Why it keeps happening

Why it keeps happening

Three things we can measure in the data. None of them proves a cause on its own, but each points at a different kind of infrastructure problem.

Indicator 1
5Dry
overflows spilling with no rain to excuse it

A discharge in dry weather is not an exceptional circumstance, so it is not permitted on any reading of regulation 4.

See the 5 →
Indicator 2
0Overloaded
works whose estimated load sits above their permitted flow

A strong signal, not a finding. We cannot see whether flow is transferred to another works for treatment, and the permitted figure is not always published.

See the 0 →
Indicator 3
3Early
overflows that spilled while their works stayed shut

Rainfall across the catchment does not explain a discharge that an overflow's own treatment works did not share.

See the 3 →

Where the indicators concentrate

OverflowHoursDryWhat it points toVerdict
Haye Road, CallingtonCSO4600Spills before its worksNo action
Golberdon STWSO1,7755Very long spillsOn record
Rilla Mill STWSO4595High spill frequencyNo action
Callington STWSSO1,0063Very long spillsNo action
Pensilva pumping stationPS-CSO/EO2060Spills before its worksNo action
North Hill STWSO9827Dry spillingOn record
Upton Cross, Rilla MillCSO00Spills before its worksNo action
Bathpool STWSO3997Dry spillingNo action

Hours are the last full year; dry spills are since 2020. Verdict is whether a measure is linked to the overflow — see the gaps.

What this analysis cannot see

These indicators are measured from spill timing and rainfall alone. They cannot see misconnections, the quality of effluent from a works that is running normally, flow transferred between works for treatment, a company's maintenance history, or the periods when a monitor was offline. Because a quiet monitor records nothing, every count here is a floor, not a total.