← Long Sutton Bennetts Orchard
Spill evidence · River Hub
Long Sutton Bennetts Orchard
Pumping station overflow · WXW00128 · feeds LANGPORT STW
Dry spill
Evidence strength
Medium confidence- ✓ Dry across a 3-day window
- ✓ Rain gauge close (≤5 km)
- ✓ Monitor 100% operational that year
- ⚠ Short discharge (<1 h) — weaker signal
The discharge
- Spill day
- Friday, 8 March 2024
- Started
- 8 Mar 2024, 10:40
- Ended
- 8 Mar 2024, 10:55
- Duration
- 15 minutes
- Receiving water
- King's Sedgemoor Drain - Henley Sluice to mouth
- Parish
- Long Sutton
Rainfall evidence
Daily rainfall at the matched gauge (Somerton) for the spill day and the days before. A spill is dry when every day in the window is ≤ 0.25 mm.
1-day window: Dry spill3-day window: Dry spill4-day window: Wet weather
| Date | Rainfall | |
|---|---|---|
| 08/03/2024 (spill day) | 0.029 mm | dry |
| 07/03/2024 | 0.142 mm | dry |
| 06/03/2024 | 0 mm | dry |
| 05/03/2024 | 0.1 mm | dry |
| 04/03/2024 | 7.999 mm | rain |
River flow that day: 9.27 m³/s. Verify at the EA rainfall station.
Gauge proximity
Outlet (red) vs matched rain gauge (blue), 4.7 km apart. Closer means the rainfall reading is more representative of the overflow.
Loading map…
Severity & context
- Bathing water
- Not Applicable
- Shellfish water
- Not Applicable
- Ahead of the works
- Unknown (no works overflow data)
- EA annual return (2024)
- 104 counted spills · 1934 h total
- Monitor uptime (2024)
- 100% operational
Method & provenance. Dry/wet classification is decided by rainfall at the nearest EA gauge — ≤ 0.25 mm on the spill day and each preceding day of the window (how we classify). Spill data: Environment Agency EDM (outlet WXW00128). Rainfall: EA Hydrology gauge 52a0e101-be9f-4680-aa58-529b7e728d84. A dry spill is precautionary evidence of a likely fault, not proof of an offence — we test the rainfall, not the works' flow. Generated by River Parrett Data.